While power cuts eat into your profits, an inefficient DG set will simply add to your losses. Powered by Powerol engines, Mahindra Powerol DG sets have been designed to ensure you an efficient power supply. This also assures you years of hassle-free operations.
PARAMETERS | 75KV TO 200KV | ||||||||
Variants | 75 | 82.5 | 100 | 125 | 160 | 180 | 200 | ||
Power rating [KW] | 60 | 66 | 80 | 100 | 128 | 144 | 160 | ||
No. of phase | 3 Phase | ||||||||
Output Voltage [V] | 415 V | ||||||||
Power Factor [lagging] | 0.8 | ||||||||
Current [A] [1 Phase/ 3 Phase] | 104 | 115 | 139 | 174 | 223 | 251 | 278 | ||
Frequency[HZ] RPM | 50/1500 | ||||||||
Governing Class | A1 | G2 as per ISD 8528 part V | |||||||
Starting Class | 12V DC Electrical | 24V DC Electrical | |||||||
Fuel Tank Capacity [lit] | 180 | 200 | 219 | 300 | 400 | ||||
Gensets Dimensions w/o Sliencer [LxWxH*][mm] approx | 3000*1150*2135 | 2950*1075*1575 | 3200*1200*1600 | 3500*1230*1425 | 3750*1300*1800 | 4300*1400*1800 | |||
Gensets Weight [kg] | 1350 | 1700 | 1750 | 1900 | 2350 | 2750 | 2800 | ||
Engine Specifications | Make | Mahindra | Mahindra mPOWER | ||||||
Model | 41035 GM C2 | mPower41015G | mPower41265G | mPower61565G | mPower61995G | mPower62235G | mPower62485G | ||
Power Output*[HP] | 103* | 101 | 126 | 156 | 199 | 223 | 248 | ||
Aspiration | TCI | TCA | |||||||
No. of cylinder | 4 | 6 | |||||||
Bore & Stroke | 96*122 | 105*137 | |||||||
Displacement[cc] | 4.8 | 7.2 | |||||||
Fuel consumption 75% load [lit/hr] | 13.5 | 13.9 | 17.3 | 21.4 | 27.8 | 28.7 | 33.3 | ||
Fuel consumption 100% load | 17.8 | 18.1 | 23.1 | 28 | 36.7 | 38.2 | 40.8 | ||
Lube oil specification | SAE15W40 CI4 | SAE15W40 API CI4+ | |||||||
Total Lube oil system capacity | 10 | 13.5 | 20.2 | ||||||
Lube oil capacity [lit/hr] | 0.15% Fuel Consumption | 0.1% Fuel Consumption | |||||||
Lube oil chnage peroid [hr.] | 300 hrs. for top up, 600 hrs for oil change | 500 hrs for oil change | |||||||
Radiator coolent capacity[liters] | 19 | 22.5 | 25 | 24 | |||||
Alternator Specifications | Make | Mahindra Powerol | |||||||
Enclosure Type | IP23 | ||||||||
Voltage regulation | -+1% | ||||||||
Class of insulation | Class H | ||||||||
Maximum Unbalanced load across Phases | 25% |